Daikin Altherma 3 R F Installer's Reference Manual page 35

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03
a
b c d e
g
M
n
  5‒0
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Pump
f
Shut-off valve
g
Motorised 3‑way valve
h
Non-return valve (field supply)
i
Shut-off valve (field supply)
j
Collector (field supply)
k
Auxiliary boiler (field supply)
l
Aquastat valve (field supply)
m
DHW tank
n
Heat exchanger coil
FHL1...3
Under floor heating
NOTICE
Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
Make sure the return water to the heat pump does NOT exceed 55°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 55°C.
-
Install an aquastat valve in the return water flow of the heat  pump. Set the
aquastat valve to close above 55°C and to open below 55°C.
Install non-return valves.
Make sure to only have one expansion vessel in the water circuit. An expansion
vessel is already pre-mounted in the indoor unit.
Install the digital I/O PCB (option EKRP1HBAA).
Connect X1 and X2 (changeover to external heat source) on the digital I/O PCB to
the auxiliary boiler. See
4
source" [
 103].
To setup the heat emitters, see
4
system" [
 23].
5
f
h
j
h
f
i
k
l
i
FHL1
FHL2
m
"7.9.15  To connect the changeover to external heat
"5.2  Setting up the space heating/cooling
Application guidelines
|
FHL3
Installer reference guide
35