Daikin Altherma 3 R F Installation Manual

Daikin Altherma 3 R F Installation Manual

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

Installation manual
Daikin Altherma 3 R F
EHVZ04S18E*6V
EHVZ08S18E*6V
EHVZ08S23E*6V
Installation manual
EHVZ08S18E*9W
English
Daikin Altherma 3 R F
EHVZ08S23E*9W

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R F

  • Page 1 Installation manual Daikin Altherma 3 R F EHVZ04S18E*6V EHVZ08S18E*6V EHVZ08S23E*6V Installation manual EHVZ08S18E*9W English Daikin Altherma 3 R F EHVZ08S23E*9W...
  • Page 2 3P633779-3...
  • Page 3: Table Of Contents

    7.2.5 Configuration wizard: Main zone......... 26 Latest revisions of the supplied documentation may be available on 7.2.6 Configuration wizard: Additional zone......27 the regional Daikin website or via your dealer. 7.2.7 Detailed screen with weather-dependent curve..27 EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A –...
  • Page 4: Specific Installer Safety Instructions

    Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). Specific installer safety 1°...
  • Page 5 When the water commissioning checklist is also available on the Daikin temperature in the main zone is too high, the contact will Business Portal (authentication required).
  • Page 6: About The Box

    3.1.2 To handle the indoor unit Use the handles at the back and at the bottom to carry the unit. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 7 ▪ Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes. WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. NOTICE ▪...
  • Page 8 ▪ Top opening: The area of the top opening must be larger than or equal to the bottom opening. The bottom of the top opening must be situated at least 1.5 m above the top of the bottom opening. ▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold). Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 9: Opening And Closing The Unit

    During the installation, you will need access to the inside of the indoor unit. To have easier front access, put the switch box lower on the unit as follows: EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 10: To Close The Indoor Unit

    3 Slide the indoor unit into position. 4 Adjust the height of the leveling feet to compensate for floor irregularities. The maximum allowed deviation is 1°. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 11: Piping Installation

    RH 80%, the thickness of the insulation materials should be at least 20  mm to prevent condensation on the surface of the insulation. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 12: Connecting Water Piping

    4 Reattach the top panel. 5.4.3 To fill the water circuit To fill the water circuit, use a field supply filling kit. Make sure you comply with the applicable legislation. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 13: To Fill The Domestic Hot Water Tank

    Tightening torques Item Tightening torque (N•m) M4 (X1M) 1.2~1.5 M4 (earth) Connections to the indoor unit Item Description Power supply (main) "6.3.1 To connect the main power supply" [ 4  14]. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 14: To Connect The Main Power Supply

    2 Connect the main power supply. Wires: 2×(0.75~1.25 mm²) In case of normal kWh rate power supply Maximum length: 500 m Interconnection Wires: (3+GND)×1.5 mm² [2.9] Control cable (= main power supply) [1.6] Room sensor offset — Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 15 The preferential kWh rate power supply contact is connected to the same terminals (X5M/9+10) as the safety thermostat. Thus, system have EITHER preferential kWh rate power supply OR a safety thermostat. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 16: To Connect The Backup Heater Power Supply

    3N~, 50 Hz L1 L2 L3 400 V AC Q1DI Factory-mounted cable connected to the contactor of the backup heater, inside the switch box (K1M) Field wiring (see table below) Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 17: To Connect The Shut-Off Valve

    2 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 18: To Connect The Domestic Hot Water Pump

    Do NOT change. 3 Fix the cable with cable ties to the cable tie mountings. 3 Fix the cable with cable ties to the cable tie mountings. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 19: To Connect The Space Heating On/Off Output

    Minimum load: 20 mA, 5 V DC [9.C] Bivalent unit" [ 4  9]): 1 Open the following (see "4.2.1 To open the indoor 1 Top panel 2 User interface panel 3 Upper switch box cover EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 20: To Connect The Safety Thermostat (Normally Closed Contact)

    [9.8.1]=3 (Benefit kWh power supply = Safety appropriate terminals as shown in the illustration below. thermostat) 4 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 21: To Connect A Smart Grid

    ▪ In case of high voltage Smart Grid contacts This requires the installation of the Smart Grid relay kit 3 Fix the cables with cable ties to the cable tie mountings. (EKRELSG). EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 22 Wires between the relays and X10M (AWG18 RED) 1 2 3 4 X10M 5 6 9 10 X10M 1 2 3 4 2 Connect the low voltage wiring as follows: Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 23: To Connect The Wlan Cartridge (Delivered As Accessory)

    (via the unit), the configuration wizard Advanced user pin code starts to help you configure the system. The Advanced user pin code is 1234. Additional menu items for the user are now visible. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 24: Configuration Wizard

    When confirmed, the system will restart and recent We recommend to set Emergency to Automatic if the house is changes will be applied. unattended for longer periods. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 25: Configuration Wizard: Backup Heater

    [6‑03]+[6‑04]. ▪ the zone with the highest water temperature is configured as the additional zone. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 26: Configuration Wizard: Main Zone

    T. the storage temperature setpoint is higher than 50°C, Example radiators: 40–10/2=35°C Daikin recommends NOT to disable the backup heater Example underfloor heating: 40–5/2=37.5°C second step because it will have a big impact on the required time for the unit to heat up the domestic hot water To compensate, you can: tank.
  • Page 27: Configuration Wizard: Additional Zone

    Item Description to equally increase the leaving water temperature for all ambient WD curve before changes. temperatures. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 28: Configuration Wizard: Tank

    The storage economic temperature denotes the lower desired tank temperature. It is the desired temperature when a storage economic action is scheduled (preferably during day). Code Description Eco setpoint: [5.3] [6-0B] ▪ 30°C~min(50,[6‑0E])°C Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 29: Weather-Dependent Curve

    To operate weather dependent, correctly configure the setpoint of the main zone, additional zone or tank. See curves" [ 4  30]. "7.3.4 Using weather-dependent 7.3.2 2-points curve Define the weather-dependent curve with these two setpoints: EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 30: Using Weather-Dependent Curves

    Confirm changes and return to the submenu. temperatures … temperatures … Cold ↑ — 7.3.4 Using weather-dependent curves ↓ — Configure weather-dependent curves as following: Cold ↓ ↑ Cold Cold — ↑ Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 31: Settings Menu

    External room thermostat at additional zone ▪ [C‑07]=1 (External room thermostat) User interface at indoor unit External room thermostat at main zone External room thermostat at additional zone EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 32: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 33: Commissioning

    The refrigerant pipes (gas and liquid) are thermally commissioning instructions in this chapter, a general insulated. commissioning checklist is also available on the Daikin Business Portal (authentication required). The correct pipe size is installed and the pipes are properly insulated.
  • Page 34: To Perform An Air Purge

    1 Set the user permission level to Installer. See "To — ▪ DHW pump test level" [ 4  23]. change the user permission 2 Go to [A.1]: Commissioning > Operation test run. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 35: To Perform An Underfloor Heating Screed Dryout

    ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 36: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 37: Wiring Diagram: Indoor Unit

     External thermistor PHC1 (A4P) * Optocoupler input circuit  Heat pump convector  Heat pump convector Thermal protector backup heater Q3L, Q4L # Safety thermostat Q*DI # Earth leakage circuit breaker EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 38 Only for *** Only for wireless On/OFF Only for wireless On/OFF thermostat thermostat (3) User interface (3) User interface Electrical connection diagram For more details, please check the unit wiring. Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 39 & add: X2M: 3-4 demand input 4 signal 2 core Only for remote user interface 2x0.75 X5M: 11-12 A14P: P1-P2 user interface communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D130331A EHVZ04+08S18+23EA6V+9W Installation manual Daikin Altherma 3 R F 4P629092-1A – 2020.08...
  • Page 40: Indoor Unit

    , consider the value that corresponds to room "A =12 m ". room 10.4 Table 2 – Minimum floor area: indoor unit (kg) Minimum floor area (m²) H=600 mm 1.84 28.81 1.86 29.44 1.88 30.08 1.90 30.72 Installation manual EHVZ04+08S18+23EA6V+9W Daikin Altherma 3 R F 4P629092-1A – 2020.08...