5.6 Setting up the power consumption control

ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03
Setup
Connect power meter 1 to X5M/5 and X5M/6.
Connect power meter 2 to X5M/3 and X5M/4.
See
"7.9.11 To connect the electricity
Power meter types
Power meter  1: Single- or three-phase power meter according to the power
supply of the outdoor unit.
Power meter 2:
-
In case of a single-phase backup heater configuration, use a single-phase
power meter.
-
In other cases, use a three-phase power meter.
Example
Single-phase outdoor unit with a three-phase backup heater:
0
0
58 0
1 5 0
a
c
e
e
f
g
h
i
A
B
A
Outdoor unit
B
Indoor unit
C
DHW tank
a
Electrical cabinet (L
b
Electrical cabinet (L
c
Power meter (L
/N)
1
d
Power meter (L
/L
1
e
Fuse (L
/N)
1
f
Fuse (L
/L
/L
/N)
1
2
3
g
Outdoor unit (L
/N)
1
h
Indoor unit (L
/N)
1
i
Backup heater (L
The power consumption control:
-
Allows you to limit the power consumption of the entire system (sum of
outdoor unit, indoor unit and backup heater).
-
Configuration: Set the power limitation level and how it has to be achieved via
the user interface.
The power limitation level can be expressed as:
-
Maximum running current (in A)
-
Maximum power input (in kW)
The power limitation level can be activated:
-
Permanently
-
By digital inputs
4
meters" [
0
0
58 0
1 5 0
b
d
  
 
/N): Preferential kWh rate power supply
1
/L
/L
/N): Normal kWh rate power supply
1
2
3
/L
/N)
2
3
/L
/L
/N)
1
2
3
5
Application guidelines
|
 102].
Installer reference guide
43