8
|
Configuration
Installer reference guide
154
INFORMATION
During disinfection of the domestic hot water tank, the DHW  temperature can
exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the applicable legislation.
#
Code
[5.8]
[6-0E]
Hysteresis
The following ON hysteresis can be set.
Heat pump ON hysteresis
Applicable when domestic hot water preparation is reheat only. When the tank
temperature drops below the reheat temperature minus the heat pump ON
hysteresis temperature, the tank heats up to the reheat temperature.
The minimum ON temperature is 20°C, even if setpoint hysteresis is smaller than
20°C.
#
Code
[5.9]
[6-00]
Reheat hysteresis
Applicable when domestic hot water preparation is scheduled+reheat. When the
tank temperature drops below the reheat temperature minus the reheat hysteresis
temperature, the tank heats up to the reheat temperature.
#
Code
[5.A]
[6-08]
Setpoint mode
#
Code
[5.B]
N/A
Description
Maximum:
The maximum temperature that users can select
for the domestic hot water. You can use this
setting to limit the temperature at the hot water
taps.
The maximum temperature is NOT applicable
during disinfection function. See disinfection
function.
Description
Heat pump ON hysteresis
2°C~40°C
Description
Reheat hysteresis
2°C~20°C
Description
Setpoint mode:
Fixed
Weather dependent
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03