Installation Site Requirements Of The Indoor Unit - Daikin Altherma 3 R F Installer's Reference Manual

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

6.2.3 Installation site requirements of the indoor unit

ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03
1
3
a
Suction grille
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
e
EKFT008D option kit
In any case, provide at least 300  mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100  mm above the maximum expected
level of snow. See
"7.3 Mounting the outdoor
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
INFORMATION
Also read the precautions and requirements in the "General safety precautions"
chapter.
2
a
c
b
e
4
unit" [
6
Preparation
|
a
 70] for more details.
Installer reference guide
51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents