Application guidelines
5.2.3 Multiple rooms – Two LWT zones
Installer reference guide
32
Setting
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
If the heat emitters selected for each room are designed for different leaving water
temperatures, you can use different leaving water temperature zones (maximum
2).
In this document:
▪
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
▪
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
CAUTION
If there is more than one leaving water zone, ALWAYS install a mixing valve station in
the main zone to decrease (in heating)/increase (in cooling) the leaving water
temperature when the additional zone has demand.
Typical example:
Room (zone)
Living room (main zone)
Bed rooms (additional zone)
Setup
A Additional leaving water temperature zone
B Room 1
C Room 2
0 (Single zone): Main
Heat emitters: Design temperature
Underfloor heating:
▪
In heating: 35°C
▪
In cooling: 20°C (only refreshment, no
real cooling allowed)
Heat pump convectors:
▪
In heating: 45°C
▪
In cooling: 12°C
A
C
B
a
D
c
E
d
b