Combination: Underfloor heating + Heat pump convectors
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03
Space heating is provided by:
-
The underfloor heating
-
The heat pump convectors
Space cooling is provided by the heat  pump convectors only. The underfloor
heating is shut off by the shut-off valve.
Setup
A Main leaving water temperature zone
B One single room
a Remote controller of the heat pump convectors
The heat pump convectors are directly connected to the indoor unit.
A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.
The desired room temperature is set via the remote controller of the heat pump
convectors.
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent by one digital output (X2M/4 and X2M/3) on
the indoor unit to:
-
The heat pump convectors
-
The shut-off valve
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
5
A
B
M1
a
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Application guidelines
|
Value
Installer reference guide
27