Installation Site Requirements Of The Indoor Unit - Daikin Altherma 3 R MT F Series Installer's Reference Manual

Table of Contents

Advertisement

7
|
Unit installation

7.1.3 Installation site requirements of the indoor unit

Installer reference guide
54
c
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
In any case, provide at least 150  mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100  mm above the maximum expected
level of snow. See
"7.3 Mounting the outdoor
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
INFORMATION
Also read the precautions and requirements in the
4
precautions" [
The indoor unit is designed for indoor installation only and for the following
ambient temperatures:
-
Space heating operation: 5~30°C
-
Space cooling operation: 5~35°C
-
Domestic hot water production: 5~35°C
Mind the following measurements guidelines:
Maximum refrigerant piping length
outdoor unit
Minimum refrigerant piping length
outdoor unit
Maximum height difference between indoor unit and outdoor
unit
(a)
Refrigerant piping length is the one-way length of liquid piping.
Mind the following spacing installation guidelines:
CAUTION
Install the indoor unit at a minimum distance of 1 m from other heat sources (>80°C)
(e.g. electrical heater, oil heater, chimney) and combustible materials. Otherwise the
unit may be damaged or in extreme cases catch fire.
a
c
b
unit" [
 10].
(a)
between indoor unit and
(a)
between indoor unit and
4
 71] for more details.
"2  General safety
50 m
3 m
30 m
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05