Power Cables - Huawei UPS5000-A-400 kVA User Manual

50 kva, pf 0.9
Hide thumbs Also See for UPS5000-A-400 kVA:
Table of Contents

Advertisement

UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)

3.1.6 Power Cables

Table 3-5 Recommended cross-sectional areas for power cables
Issue 03 (2020-01-10)
The UPS can generate large leakage currents. A circuit breaker that provides leakage
current protection is not recommended.
If UPSs are connected in parallel, input and output power cables for each UPS should have
the same length and specifications.
Item
Mains input
Mains input current (A)
connector
Recommended cross-
sectional area (mm
Bypass input
Bypass input current (A)
connector
Recommended cross-
sectional area (mm
Output
Output current (A)
connector
Recommended cross-
sectional area (mm
Battery input
Nominal discharge current (384 V current;
connector
thirty-two 12 V batteries) (A)
Maximum discharge current (end of
discharge current of thirty-two 12 V
Copyright © Huawei Technologies Co., Ltd.
L1
2
)
L2
L3
N
PE
L1
2
)
L2
L3
N
PE
U
2
)
V
W
N (Increase the
cross-sectional
area at non-linear
load)
PE
3 Installation
400 kVA
675
2 x (4 x 240)
240
608
2 x (4 x 240)
240
608
2 x (4 x 240)
240
1042
1246
54

Advertisement

Table of Contents
loading

Table of Contents