4.2.5 Maint. Page

On the homepage, click the Maint. tab. The Maint. page provides the Calib.,
Commissioning Var., Upgrade, and Download tabs. The Maint. page consists of three parts,
Issue 03 (2020-01-10)
The default SNMP version is V3. The preset password is Changeme1 for MD5/SHA and is
Changeme2 for DES/AES. Change the password after your first login, preventing unauthorized
access.
The standard protocols SNMP V1 and SNMP V2 have security risks. You are advised to use the
secure protocol SNMP V3.
The standard encryption algorithms MD5 and DES have security risks. You are advised to use the
secure encryption algorithms SHA and AES.
To obtain the MIB file choose Config > Site Config > SNMP > Download HUAWEI_UPS_MIB.
SNMP Trap indicates the IP address of the server configured with NMS software. If SNMP Trap is
incorrectly set or not set, system information will be lost or not reported in time.
The certificate is used for Secure Sockets Layer (SSL) encryption protection during WebUI login.
Apply to a third-party institution for the certificate.
Specify Email server IP address, Sender's email, and User account authentication required
when sending a mail and click Test to check whether the test email can be received. Configure
Alarm Notification Server is used to configure a server for receiving alarm emails from the
monitoring system.
Set Email and Alarm Severity and simulate an alarm. Check that the alarm email can be received.
Configure Alarm Notification Email Address is used to configure the email address for receiving
alarm emails from the monitoring system.