3.2.1.2
Power Input
Rated Voltage: 24VDC (±20%)
Dual Power Input: Supported
Max Current on Bus: 2A
Diagnosis Function:
Over/under voltage for input 1&2
Over current output on bus
Over Voltage LED Alarm: Around 28.8V
Over Voltage Shutdown: Around 36V
Under Voltage LED Alarm: Around 19.2V
Under Voltage Shutdown: Around 9V
3.2.1.3
EtherCAT Coupler
Function: Coupling EtherCAT IO modules to 100BASETX EtherCAT network
Cable: Ethernet/EtherCAT cable (min. Cat. 5), shielded
Distance between stations: Max. 100 m (100BASETX)
Number of configurable IDs: 256 (2 x 16-bit ID switch)
Bus Interface: 2 x RJ45 (1 x Input, 1 x Output)
3.2.1.4
Environment
Operation Temperature: -10~60°C (vertical mounted)
Storage Temperature: -40~85°C
Relative Humidity: 5~95% (non-condense)