Minimum Firebox Clearances Diagram
The following diagram shows the minimum clearances to the sides and back of any built-in Ortal fireplace.
LEGEND:
Non-combustible material such as 5/8"
Type X fire rated drywall (or equivalent)
Combustible material
NOTES:
•
The clearances mentioned in the diagrams on the immediately previous page apply to the front of the
firebox.
•
The 12" clearance spans from the top of the fireplace viewing area to the bottom of the framing.
•
The 9-13/16" clearance spans from the bottom of the legs to the bottom of the fireplace viewing area. Legs
are not removable or adjustable.
•
While not shown in this diagram, a heat release is required for all built-in Ortal fireplaces (see section
labeled "Heat Release" details). An air intake is also required for all built-in Ortal fireplaces with the double
glass heat barrier (see section labeled "Air Intake" details).
•
No building material is permitted to touch the vent pipe. Only tested, listed and approved components are
permitted to touch the pipe.
Ortal Installation Manual: Built-in Models, December 2019 (V2)
Wood framing
Metal framing
25