Horizontal Termination Venting Diagram
Use this diagram and tables below to calculate distances for venting runs that terminate horizontally.
Series 40-75
V minimum = 3 feet
Max
Vertical
Horizontal
(V)
(H)
3 ft
21 ft
6 ft
24 ft
9 ft
24 ft
12 ft
24 ft
15 ft
24 ft
18 ft
21 ft
21 ft
18 ft
24 ft
15 ft
27 ft
12 ft
30 ft
12 ft
33 ft
12 ft
NOTES:
•
It is no longer required to maintain ¼" of rise per foot of pipe.
•
For venting runs that exceed these maximums, consider Ortal's Power Vent System. See the Ortal Power
Vent Manual for details.