Horizontal Termination Venting Diagram - ORTAL 40 Series Installation And Operation Manual

Built-in models
Table of Contents

Advertisement

Horizontal Termination Venting Diagram

Use this diagram and tables below to calculate distances for venting runs that terminate horizontally.
Series 40-75
V minimum = 3 feet
Max
Vertical
Horizontal
(V)
(H)
3 ft
21 ft
6 ft
24 ft
9 ft
24 ft
12 ft
24 ft
15 ft
24 ft
18 ft
21 ft
21 ft
18 ft
24 ft
15 ft
27 ft
12 ft
30 ft
12 ft
33 ft
12 ft
NOTES:
It is no longer required to maintain ¼" of rise per foot of pipe.
For venting runs that exceed these maximums, consider Ortal's Power Vent System. See the Ortal Power
Vent Manual for details.
Ortal Installation Manual: Built-in Models, December 2019 (V2)
SERIES 110-130
V minimum = 3 feet
Max
Vertical
Horizontal
(V)
(H)
3 ft
12 ft
6 ft
18 ft
9 ft
24 ft
12 ft
21 ft
15 ft
21 ft
18 ft
18 ft
21 ft
15 ft
24 ft
12 ft
27 ft
12 ft
30 ft
12 ft
33 ft
12 ft
Series 150-170
& Traditional
V minimum = 3 feet
Max
Vertical
Horizontal
(V)
(H)
3 ft
9 ft
6 ft
12 ft
9 ft
18 ft
12 ft
21 ft
15 ft
18 ft
18 ft
18 ft
21 ft
15 ft
24 ft
12 ft
27 ft
9 ft
30 ft
9 ft
33 ft
9 ft
Series 200-250
V minimum = 6 feet
Max
Vertical
Horizontal
(V)
(H)
N/A
N/A
6 ft
9 ft
9 ft
12 ft
12 ft
12 ft
15 ft
15 ft
18 ft
15 ft
21 ft
12 ft
24 ft
12 ft
27 ft
9 ft
30 ft
9 ft
33 ft
6 ft
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents