Complying With Degree Of Protection Ip65/Ip67; Voltage Supply - Festo CPX-FB37 Translation Of The Original Instructions

Hide thumbs Also See for CPX-FB37:
Table of Contents

Advertisement

3
Mounting and installation
Cable specification
Cable type
Transmission class
Cable diameter
Core cross section
Connection length
1) Required for maximum connection length between network participants
Tab. 3.8 Cable specification overview
3.4

Complying with degree of protection IP65/IP67

In order to comply with degree of protection IP65/IP67, seal the ports with the following plugs or cover
caps:
Port
X1 In, X2 Out (M12)
Service interface (M12)
1) if connection is unused
2) included in the scope of delivery
Tab. 3.9 Ports, plugs and cover caps for degree of protection IP65/IP67
3.5

Voltage supply

Warning
Danger of electric shock from voltage sources without protective measures.
• Only use PELV circuits in accordance with IEC/EN 60204-1 (protective extra-low
voltage, PELV) for the electrical power supply.
• Also observe the general requirements for PELV circuits in accordance with
IEC/EN 60204-1.
• Only use voltage sources which ensure reliable electrical isolation of the operating
voltage in accordance with IEC/EN 60204-1.
Through the use of PELV circuits, protection against electric shock (protection against direct and indir-
ect contact) is ensured in accordance with IEC/EN 60204-1.
The current consumption of a CPX terminal depends on the number and type of integrated modules and
components.
24
Ethernet twisted pair cable, shielded (Shielded Twisted Pair, STP)
Category Cat 5 or higher
6 ... 8 mm
2
0.14 ... 0.75 mm
; 22 AWG
Maximum 100 m
Plug
NECU-M-S-D12G4-C2-ET
– Plug of the operator unit
(CPX-MMI)
– Plug of the USB adapter for
CPX-FMT
1)
1)
Cover cap
ISK-M12
2)
ISK- M12
Festo – P.BE-CPX-FB37-EN – 1406NH – English