Festo CPX-FB37 Translation Of The Original Instructions page 60

Hide thumbs Also See for CPX-FB37:
Table of Contents

Advertisement

5
Diagnostics
M (modify) – parameterisation, forcing
LED (yellow)
Sequence
ON
OFF
LED
not illuminated
ON
OFF
LED illuminated
ON
OFF
LED flashes
1) The display of the Force function (LED flashes) has priority over the display of the setting for the system start (LED lights up).
Tab. 5.6 LED display "M"
60
Status
"System start with default
parametrisation and
current CPX expansion" is
set (factory setting);
external parameterisation
is possible
"System start with saved
parameterisation and
saved CPX expansion" is
set; parameters and CPX
expansion are saved
remanently; external
parameterisation is
1)
blocked
1)
Force is active
Significance / error handling
Caution when replacing bus nodes
with saved parametrisation:
When using these bus nodes,
parameterisation of the CPX terminal
is not automatically restored by the
higher-order controller during
replacement.
• Save the required settings before
replacing the bus node and restore
the settings after replacement.
The Force function is enabled (
system descriptionP.BE-CPX-SYS...).
Festo – P.BE-CPX-FB37-EN – 1406NH – English
CPX

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents