Diagnostics
Composition of the emergency message – error register (byte 2)
1)
Bit
Meaning
0
Generic error
1
Current
2
Voltage
3
4
Communication error
5 ... 6
7
Manufacturer specific
1) Bold = Bit is used by CPX terminal
Tab. 5.18 Error register (index 1001 with bit assignment according to DS301/401)
Further diagnostic information is provided by the CPX terminal in bytes 3 ... 6 of the emergency object
(manufacturer status register, index 1002).
Composition of the emergency message – status bits (byte 3)
Bit
Meaning
0
Error at valve
1
Error at output
2
Error at input
3
Error on analogue
module/function module
4
Undervoltage
5
Short circuit/overload
6
Wire break
7
other error
Tab. 5.19 Manufacturer status register – status bits
Composition of the emergency message – CPX module number (byte 4)
Bit
Meaning
0 ... 7
CPX module number
Tab. 5.20 Manufacturer status register – CPX module number
74
Explanation
Bit is set for each error
– Short circuit/overload in sensor supply
– Short circuit/overload at the outputs
– U
(undervoltage of outputs)
OUT
– U
(undervoltage of valves)
VAL
– Failure of load voltage at CPX output module or
input module
Node guard, heartbeat, fieldbus-specific only
– Wire break
– other error
Explanation
Module type in which an error has occurred
Error type
Explanation
Number of the module with diagnostic message