Setting The Cc-Link Station Number And The Baudrate; Station Number; Baudrate; Error Messages - Pepperl+Fuchs VBG-CCL-G4F Manual

As-interface/cc-link gateway ip67
Table of Contents

Advertisement

After the address has been successfully set, the next faulty assignment is display-
ed and the address assignment can begin from the start. Otherwise, the system
displays an error code (chapter 11). When all faulty assignments are eliminated
the display is empty.
6.6

Setting the CC-Link Station Number and the Baudrate

6.6.1

Station Number

The addressing of the AS-i/CC-Link-Gateway as a CC-Link Remote Device can be
done locally on the gateway. To change the station number both the "set" button
and the "mode" button have to be pushed simultaneously for at least 5 seconds
until the current station number is shown on the LED display. With every pushing
of the "set" button, the station number can now be increased by 1.
Once the desired station number is shown on the display, it will be stored non-vo-
latile in the EEPROM by pushing the "mode" button.
On the AS-i/CC-Link-Gateway, station numbers from 1 to 62 can be selected.
When delivered the station address is set to 1.
6.6.2

Baudrate

After the station address has been set, the code for the baudrate (see table) will
be displayed.
Code
0
1
2
3
4
The baudrate can be changed with the button "set" and be stored with the button
"mode".
After the setting of station address and baudrate is finished, the normal display ap-
pears again and the AS-i master is ready to operate.
When delivered the baudrate is set to 156kbps.
6.7

Error Messages

Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Operating the AS-i/CC-Link Gateway
Baudrate
156 kbps
625 kbps
2.5 Mbps
3 Mbps
10 Mbps
The system displays error codes for error messages that do not
point to faulty assignments on the AS-i circuit. The code numbers