Set_Permanent_Parameter (Set_Pp); Get_Permanent_Parameter (Get_Pp); Write Parameter (Write_P) - Pepperl+Fuchs VBG-CCL-G4F Manual

As-interface/cc-link gateway ip67
Table of Contents

Advertisement

9.1.2.4

Set_Permanent_Parameter (SET_PP)

With this call, a parameter value for the specified AS-i slave is configured on the
AS-i/CC-Link Gateway. The value is stored permanently in the EEPROM of the
Gateway.
The configured parameter is not transferred immediately by the AS-i/CC-Link Ga-
teway to the AS-i slave. The configured parameter value is only transferred when
the AS-i slave is activated after turning on the power supply on the AS-i/CC-Link
Gateway.
byte
1
2
3
4
byte
1
2
9.1.2.5

Get_Permanent_Parameter (GET_PP)

With this call, a slave-specific parameter value stored on the EEPROM of the
AS-i/CC-Link Gateway is read.
byte
1
2
3
byte
1
2
3
9.1.2.6

Write Parameter (WRITE_P)

The AS-i slave parameter value transferred with the command is passed on to the
addressed AS-i slave.
The parameter is stored on the AS-i/CC-Link Gateway only temporarily and is not
entered as a configured parameter in the EEPROM!
The AS-i slave transfers its current parameter value in the response (parameter
echo). This can deviate from the value that has just been written according to the
Subject to reasonable modifications due to technical advances.
36
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
7
6
5
2
2
2
T
B
7
6
5
2
2
2
T
7
6
5
2
2
2
T
B
7
6
5
2
2
2
T
Request
4
3
2
2
43
16
circuit
slave address
Response
4
3
2
2
43
16
result
Request
4
3
2
2
01
16
circuit
slave address
Response
4
3
2
2
01
16
result
AS-Interface
Mailbox
2
1
0
2
2
2
PP
2
1
0
2
2
2
2
1
0
2
2
2
2
1
0
2
2
2
PP
Copyright Pepperl+Fuchs, Printed in Germany