Operating the AS-i/CC-Link Gateway

6.1

Master Start-Up

After powering on, all segments of the figure display and all LEDs light up for ap-
proximately one second (self-test). Afterwards, the LEDs display the condition of
their respective flags. The figure display shows the condition of the master:
40 Off-line Phase
The AS-i master initializes - there is no data communication on the AS-i.
In configuration mode automatically the device can leave the off-line
phase.
In protected mode, if the CC-Link communication is interrupted, the AS-i
master switches to the off-line phase after the watchdog time of the CC-
Link has expired and was started automatically.
41 Detection Phase
Start of the start-up phase, where the system looks for slaves located on
the AS-i. The master remains in the detection phase until it finds at least
one slave.
1
42
Activation Phase
Condition at the end of the start-up operation where the parameters are
transmitted to all connected and recognized slaves. This enables access
to the AS-i slaves' data connections.
2
43
Start of Normal Operation
In normal operation the AS-i master can exchange data with all active
slaves. It transmits management messages and looks for and activates
newly connected slaves. During normal operation, the system keeps the
maximum cycle time of 5 milliseconds.
6.2

Configuration Mode

The configuration mode serves to configure the AS-i circuit.
1. Activation phase and the start of normal operation maybe so short that the numbers can not be seen in the display.
2. Activation phase and the start of normal operation maybe so short that the numbers can not be seen in the display.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Operating the AS-i/CC-Link Gateway
If the AS-i circuit is insufficiently powered ("U AS-i"
does not light up) or there is no communication relation-
ship between the CC-Link master and the CC-Link gateway,
the master remains in the off-line phase.
In the configuration mode, all recognized slaves are activated even
when the desired and actual configurations do not match.
AS-i/CC-Link Gateway
Copyright Pepperl+Fuchs, Printed in Germany