Nominal Ratings; Emergency Stop - Deif ASC Series Commissioning Manual

Automatic sustainable controller
Table of Contents

Advertisement

ASC commissioning guide 4189341077 UK
Menu
Function
6002
Adjust the rating of the installed
PV Panels.
6005
Adjust the Q rating of the
inverter
6006
Adjust the S rating of the
inverters.
The emergency stop will send a 0 kW reference to the PV plant and open the PV breaker if it is present.
The fail class can be selected to warning if the alarm input has to be used for other purpose.
Menu
Function
3490
Emergency stop details
3491 Timer
3492 Relay output for PLC
3493 Relay output for PLC
3494 Enable this alarms
3495 Select fail class
DEIF A/S

Nominal ratings

Comments
For example 200 250 Wp modules are
installed. Adjust in this menu
200*250*10^-3=50 kW.
If given. Otherwise, adjust to the same
value as 6006.
For example three 20 kVA inverters are
installed. Adjust this menu to 3*20=60
kVA.

Emergency stop

Comments
Emergency stop alarm consists of sub
menus.
If used as e-stop then select 0 sec.
OA
OB
If used as e-stop, then select S/D.
Page 23