Ma Values; Testing Procedure Of The Transducer Signals - Deif ASC Series Commissioning Manual

Automatic sustainable controller
Table of Contents

Advertisement

ASC commissioning guide 4189341077 UK

4-20 mA values

It is strictly necessary to adjust the 4-20 mA values of the connected transducer. This is done like the
following example for a 4-20 mA mains transducer with the configuration of:
Power import from grid
Power export to grid
Press the dotted line in front of the value to modify it.

Testing procedure of the transducer signals

It is essential to test the transducer signals into the DEIF controller. Please follow these steps to verify the
good functionality. All 4-20 mA inputs may be used. In the example, the mains power transducer is used
(multi-configurable input 102).
Terminal
102
103
104
DEIF A/S
Power [kW]
700 kW
-700 kW
Designation
Not used
+ (4-20)
0 (com)
Current out [mA]
20 mA
4 mA
Page 11
of 26