ASC commissioning guide 4189341077 UK
4.
Set up the translate table
a.
Set up slave ID 0 for broadcast using UDP Broadcast and route it to the IP of the inverter.
(Note that the desired slave ID address of the inverter has to be checked in the user manual of
the inverter – 126 is for example for SMA STP25000 TL).
b.
Repeat steps for the number of IP addresses you have in your system (the example below
shows a system with two (2) inverters).
c.
For remote monitoring (ASC reads from inverters), set up the translate table with your
connected inverters, for example in this case, there are two inverters where the ASC reads from
ID10 and ID11.
d.
All connected inverters must be included in the table for remote monitoring.
DEIF A/S
Page 20
of 26