Command Input/Output; Input Ifc-P/Ifc-D; Command Output Ifc-P; Command Output Ifc-D - Siemens SWT-3000 Equipment Manual

Hide thumbs Also See for SWT-3000:
Table of Contents

Advertisement

SWT 3000 Equipment Manual

Command Input/Output

Input IFC-P/IFC-D

Nominal input voltage *)
Threshold
Polarity independence
Pulse suppression
*) Regardless of the adjusted input voltage the max. voltage 287,5 V DC can be connected

Command output IFC-P

Contact type
Switching power (max.)
Switching voltage (max.)
Switching current (max.)
Switching current (max.) <2,5 ms
Carry current
Insulation withstand voltage

Command Output IFC-D

Contact type
Switching power
Switching voltage (max.)
Switching current (max.)
Carry current (max)
Insulation withstand voltage

Signaling Output IFC-S

See IFC-D
© SIEMENS AG 2008
24V – 250 V DC (tolerance -20% +15%)
70% of the adjusted input voltage (24, 48/60, 110,
250V)
Yes
1 ms (up to max.100 ms programmable in steps of 1
ms)
Relay NO
250 VA
350 V DC or peak AC
1,5 A DC or peak AC
5 A DC or peak AC
2,5 A DC or peak AC
2,5 kV rms
Relay NO, heavy duty
150 W (DC)
1250 VA (AC)
380 V DC or peak AC
220 V DC
5 A DC or peak AC (30A≤0,5ms)
5 A DC or peak AC
2,5 kV rms
Edition p3_3_2x 08/09
Technical Data
Page - 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents