SWT 3000 Equipment Manual
SWT 3000 <System-2 Configuration>
The number and type of the interface module IFC-x is defined in the <System-2 Configuration>
tab. You can configure a redundant power supply under <Power supply>. You also set the protec-
tion scheme and switch over to the test mode here.
Figure 43:

Interfaces

Only IFC-D or IFC-P modules can be inserted at slot IFC1. Slot IFC2 can also be equipped with
the IFC-D/P modules or alternatively with the IFC-S module. You will find more detailed information
about the interface modules in Chapter 4 of this equipment manual.
If using two IFC-D/P modules it is possible to use only the contact outputs from the second mod-
ule by activating <Contact doubling>, or to use also the binary inputs for the transmission of 8
commands (only via digital transmission path !).

Power supply

If the SWT 3000 is operated with two power supplies monitoring of the second power supply must
be activated under <System-2 Configuration> by selecting <Power Supply> redundant

Test mode

You switch over to test mode with the test mode setting <IFC-Test>. In this mode you can enter
commands on the IFC module for every input by means of DIL switches S1.1 to S1.4.
© SIEMENS AG 2008
Defining the IFC interface modules
Please check the <Input Configuration>!
For security reasons after switching over to test mode all inputs are sig-
nalled by the controller as "off" regardless of the actual switch position.
The "on" state can only be reached by switching all switches to the
" Open " position and then on.
Edition p3_3_2x 08/09
Installation and Commissioning
".
Page - 49