S6 Control Wires; Test Sockets; Inhibit Line - Siemens SWT-3000 Equipment Manual

Hide thumbs Also See for SWT-3000:
Table of Contents

Advertisement

CLE Module

S6 control wires

The CLE module contains an opt coupler for the S6 control wire. The S6 control wire is used for
disconnecting voice and data signals in a PLC system in alternate multi-purpose mode.
S6
b23
Figure 5:
The circuit is driven on a low-active basis. The opt coupler is activated during transmission of pro-
tection data (S6 control wire =low).

Test sockets

The following test sockets are provided on the front panel of the CLE module:
The level at the sockets is measured on a high impedance basis and corresponds to the value at
the measuring point. Incorrect operations such as short circuiting or inserting a signal (U < 5V) at
the measuring sockets does not result in interruption of teleprotection signaling.

Inhibit line

An inhibit line is routed via the CLE module which acts on the inhibit input of the power supply. If
there is no CLE module (in the case of a device with digital interfaces only) link X41 must therefore
be inserted in position 1-2 in the sub rack.
Page - 6
+5 V
Block diagram of the S6 control
1 ISEP socket for measuring the level of the receive signal
1 ISEP socket for measuring the level of the transmit signal
Edition p3_3_x 08/09
SWT 3000 Equipment Manual
+12 V
S6
© SIEMENS AG 2008

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SWT-3000 and is the answer not in the manual?

Table of Contents

Save PDF