Transmission time (SWT 3000 stand alone)*

Broad band equipment
Single purpose
Alternate multi purpose F2
Narrowband equipment
* Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are pro-
longed by about ≤ 4 ms
Operation via the PLC system ESB 2000i will prolong the transmission time by about 4ms

Transmission time (SWT 3000 integrated into PowerLink)*

Broad band equipment
Single purpose
Alternate multi purpose
F2 + AMP
Alternate multi purpose
DP + AMP
Simultaneous multipurpose
Narrow band equipments
Using speech-plus band
*Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are prolonged
by about ≤ 4 ms
Operation via the PLC system ESB 2000i will prolong the transmission time by about 4ms
© SIEMENS AG 2008
< 10ms (F6, CT)
< 15ms (F6, CT)
< 15ms (F6)
< 10ms (F6, CT)
< 15ms (F6, CT)
< 19ms (F6, CT)
< 10ms (F6, CT)
< 19ms (F6, CT)
Edition p3_3_2x 08/09
Technical Data
Page - 5