The Fobox; Interfaces Of The Fobox - Siemens SWT-3000 Equipment Manual

Hide thumbs Also See for SWT-3000:
Table of Contents

Advertisement

SWT 3000 Equipment Manual

The FOBox

The FOBox is used for connecting the SWT 3000 via optical fibre with a PDH- or SDH-Multiplexer.
For each transmission direction a separate fibre is necessary. The FO Box contains the FOM mod-
ule with the electrical/optical conversion, the interface to the multiplexer and a power supply. Fur-
ther details are described in chapter 1 of this manual.
An adaptor is installed for the conversion from the system connector to the alarm relay, the con-
nectors for the digital interface (X.21/G703.1/G703.6) and the power supply connector.
Tx - Alarm
Rx - Alarm
FO Connection
Figure 13:

Interfaces of the FOBox

The interfaces of the FOBox will be carried out by an adapter converting the pinning of the FOB
module to a 15-pin female Sub-D connector according the subsequent table.
Table 27:
DTE
Pin
Function X.21
1
Shield
2
Transmit(a)
3
Control(a)
4
Receive(a)
5
n.c.
6
Signal Timing(a)
7
n.c.
8
Signal Ground
9
Transmit(b)
10
Control(b)
11
Receive(b)
12
n.c.
13
Signal Timing(b)
14
n.c.
15
n.c.
© SIEMENS AG 2008
Selection of the
digital Interface
X.21
G703.1
G703.6
The fibre optic box
Pinning of the Sub-D female connector X1
Name X.21
Name
G.703.1
GNDS
Shield
TxD_A
TX-
C(a)
RxD_A
RX-
RxC_A
GND
G
TxD_B
TX+
C(b)
RxD_B
RX+
RxC_B
Edition p3_3_2x 08/09
Installation and Commissioning
Power supply
20-72V DC
22-60V AC
Imax=0,6A
Alarm relay
Name
Signal
G703.6
Direction
Shield
---
TX-
OUT
OUT
RX-
IN
IN
G
---
TX+
OUT
OUT
RX+
IN
IN
-
1
+
2
X4
1
2
X1
3
X2
FOB-X11
Pin
A1,A31,C1,
C31
A12
A10
A13
A11
A3
A8
A14
A9
A15
Page - 25