Table 9 PROFIDrive Compatible Status Word for the PROFIdrive Communication Profile
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4
OFF_2_STA
5
OFF_3_STA
6
SWC_ON_INHIB
7
ALARM
8
AT_SETPOINT
9
REMOTE
10
ABOVE_LIMIT
11 to 15
-
YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual
Value
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
READY TO OPERATE.
0
OFF1 ACTIVE.
1
ENABLE OPERATION.
0
DISABLE OPERATION.
1
FAULT.
0
No fault.
1
OFF2 inactive.
0
OFF2 ACTIVE.
1
OFF3 inactive.
0
OFF3 ACTIVE.
1
SWITCH-ON INHIBIT ACTIVE.
0
SWITCH-ON INHIBIT NOT ACTIVE.
1
Warning/Alarm.
0
No Warning/Alarm.
1
OPERATING. Actual value equals reference value (i.e., is within tolerance limits).
0
Actual value differs from reference value (i.e., is outside tolerance limits).
1
Drive control location: REMOTE.
0
Drive control location: LOCAL.
-
Not supported.
-
Reserved