66
A diagram of the cable routing is below.

Control cable ducts

Not allowed unless the 24 V cable is
insulated for 230 V (120 V) or
insulated with an insulation sleeving
for 230 V (120 V).
Planning the electrical installation
Input power cable
90 °
min 200 mm (8 in)
Control cables
24 V
230/120 V
Motor cable
Drive
Power cable
Lead 24 V and 230/120 V control
cables in separate ducts into the
inside of the cabinet.
ACQ800-37 Hardware Manual
min 300 mm (12 in)
Motor cable
min 500 mm (20 in)
24 V
230/120 V