Operation

These warnings are intended for all who plan the operation of the drive or operate
the drive. Ignoring the instructions can cause physical injury or death or damage the
equipment.
WARNING!
Note:
Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
Do not activate automatic fault reset functions of the Standard Control Program
if dangerous situations can occur. When activated, these functions will reset
the drive and resume operation after a fault.
Do not control the motor with the disconnecting device (means); instead, use
the control panel keys
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
Do not use the Prevention of unexpected start-up function (option +Q950) for
stopping the drive when the inverter unit(s) is running. Give a Stop command
instead.
The Safe torque off function (option +Q968) can be used for stopping the drive
in emergency stop situations. In the normal operating mode, use the Stop
command instead.
If an external source for start command is selected and it is ON, the drive (with
Standard Control Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key
.
and
, or commands via the I/O board of the drive.
11
Safety instructions