Fastening the cabinet to the floor

The cabinet is to be fastened to the floor by using clamps along the edge of the
cabinet bottom, or by bolting the cabinet to the floor through the holes inside.

Clamping

Insert the clamps into the twin slots along the front and rear edges of the cabinet
frame body and fasten them to the floor with a bolt. The recommended maximum
distance between the clamps is 800 mm (31.5 in).
If there is not enough working space behind the cabinet for mounting, replace the
lifting lugs at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
Clamp dimensions (in mm)
Cabinet frame
Cabinet frame
Slot detail, front view
(dimensions in mm)
Distances between slots
Cubicle
Distance in mm and (inches)
Width
(mm)
300
400
250 (9.85 in)
600
450 (17.7 in)
700
550 (21.65 in)
800
650 (25.6 in)
L-bracket
M16 screw
Cabinet top
Fastening the cabinet at the top with
L-brackets (side view)
150 (5.9 in)
Mechanical installation