Reset Set Value Input To Factory Setting For; Electric Closing Limit For; Reprogramming Position Of Valve At Set Value 0 V Or 0 / 4 Ma; Electric Opening Limit For - GEM 613 Installation, Operating And Maintenance Instructions

Motorized diaphragm valves, metal/plastic, dn 4-20
Table of Contents

Advertisement

Available languages

Available languages

11.2.1 RESET set value input to factory
setting for E1 / E2 / E3
Operating condition
G
→ middle LED lit (on)
Press upper and lower buttons longer
G
than 0.5 sec.
→ left and right LED lit (on); middle LED
fl ashes
Press upper and lower buttons longer
G
than 0.5 sec.
→ left and right LED lit (on); middle LED
fl ickers
→ factory setting detected
Press upper and lower buttons longer
G
than 0.5 sec.
→ middle LED lit (on)
→ factory setting is saved.
Check the new setting by changing the
G
signal.
11.2.2 Electric closing limit for E1 / E2 →

reprogramming position of valve

at set value 0 V or 0 / 4 mA
Operating condition
G
→ middle LED lit (on)
Press lower button longer than 0.5 sec.
G
→ right LED lit (on); middle LED fl ashes
Apply electric signal and change it so that
G
the motor runs to the desired position.
Press lower button longer than 0.5 sec.
G
→ right LED lit (on); middle LED fl ickers
→ new position of the valve for 0/4 mA is
detected
Press lower button longer than 0.5 sec.
G
→ middle LED lit (on)
→ new position of the valve for 0/4 mA is
saved.
Check the new setting by changing the
G
signal.
If the new valve position is not okay with a
set value of 0 / 4 mA or 0 V, a RESET must
be conducted (see chapter 11.3.1) and
the entire programming process must be
repeated.
613, 618
11.2.3 Electric opening limit for E1 / E2
→ reprogramming position of
valve at set value 20 mA
Operating condition
G
→ middle LED lit (on)
Press upper button longer than 0.5 sec.
G
→ right LED lit (on); middle LED fl ashes
Apply electric signal and change it so that
G
the motor runs to the desired position.
Press upper button longer than 0.5 sec.
G
→ left LED lit (on); middle LED fl ickers
→ new position of the valve for 20 mA is
detected
Press upper button longer than 0.5 sec.
G
→ middle LED lit (on)
→ new position of the valve for 20 mA is
saved
Check the new setting by changing the
G
signal.
If the new valve position is not okay with a
set value of 20 mA or 10 V, a RESET must
be conducted (see chapter 11.3.1) and
the entire programming process must be
repeated.
46 / 64