UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Item
Input mode

9.5 Output Electrical Specifications

Table 9-5 Output electrical specifications
Item
Rated capacity
Output PF
Rated output
voltage
Output voltage
tolerance
Total harmonic
distortion of
output voltage
(THDv)
Crest factor
Inverter
overload
capability
Issue 07 (2019-12-19)
3 kVA
125% ≤ load < 150%: 1 minute in bypass mode
Load ≥ 150%: 100 milliseconds in bypass mode
The input switch may trip in advance.
One mains input
The upper and lower thresholds are configurable on the LCD.
3 kVA
3 kVA
0.9
208 V AC, 220 V AC, 230 V AC, or 240
V AC (single-phase output; select a
voltage system by setting a voltage level
on the LCD.)
± 1%
< 4% (non-linear load)
< 2% (resistive load)
A maximum of 3:1
105% ≤ load < 125%: transfer to bypass mode after 5 minutes
125% ≤ load < 150%: transfer to bypass mode after 1 minute
Load ≥ 150%: transfer to bypass mode after 0.1 second
The UPS stops supplying power if the bypass is abnormal.
Copyright © Huawei Technologies Co., Ltd.
6 kVA
10 kVA
6 kVA
10 kVA
6 kVA
10 kVA
9 Technical Specifications
15 kVA
20 kVA
One mains input
Two mains inputs
15 kVA
20 kVA
15 kVA
20 kVA
208 V AC, 220 V AC,
230 V AC, or 240 V AC
(single-phase output;
select a voltage system by
setting a voltage level on
the LCD.)
380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the
LCD.)
100