Huawei UPS2000-G-3KRTL-V2 User Manual page 141

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Alarm ID
Alarm
(Alarm
Name
ID-Alarm
Cause)
0060-02
Inverter fault
0060-03
Inverter fault
0060-04
Inverter fault
0060-05
Inverter fault
0060-07
Inverter fault
Issue 07 (2019-12-19)
Alarm
Alarm Clear
Level
Mode
Critical Power-off clear
Critical Power-off clear
Critical Power-off clear
Critical Automatic clear
Critical Automatic clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
Repair Proposal
System
bypass mode or
technical support for repair.
has no output
based on the
transfer logic.
The UPS shuts
Possible cause: The inverter
down.
relay is faulty.
The UPS may
Measure: Contact Huawei
transfer to
technical support for repair.
another working
Possible cause: The inverter
mode or shut
output is short-circuited.
down.
Measure: Rectify output port
short circuits. After you clear
the alarm, restart the UPS. If
the alarm persists, contact
Huawei technical support for
repair.
Possible causes:
Measures:
The UPS starts
Possible causes:
upon shutdown.
The UPS may
transfer to
C Alarm Handling
The mains experiences
instantaneous
high-voltage impact.
The output has special
loads such as sensitive
loads and rectification
loads.
The output has
transformer loads but the
transformer mode is not
set.
The hardware is faulty.
After you rectify the
fault, restart the UPS.
Check whether the load
type is supported by the
UPS.
Enable the transformer
mode.
Contact Huawei technical
support for repair.
The ambient temperature
exceeds 40º C.
The air channel is
134