Huawei UPS2000-G-3KRTL-V2 User Manual page 142

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Alarm ID
Alarm
(Alarm
Name
ID-Alarm
Cause)
0060-08
Inverter fault
0061-01
Inverter alarm
0061-02
Inverter alarm
0064-01
OL timeout
0064-02
OL timeout
Issue 07 (2019-12-19)
Alarm
Alarm Clear
Level
Mode
Critical Manual
clear/Power-off
clear
Manual
Minor
clear/Power-off
clear/Automatic
clear
Minor
Manual
clear/Power-off
clear
Critical Automatic clear
Critical Manual
clear/Power-off
Copyright © Huawei Technologies Co., Ltd.
Impact on the
Repair Proposal
System
another working
mode or shut
down.
Measures:
The UPS shuts
Possible cause: The DSP or
down.
CPLD chip is faulty.
Measure: Contact Huawei
technical support for repair.
The UPS shuts
Possible causes:
down.
The UPS may
transfer to
another working
mode or shut
Measures:
down.
N/A
Possible cause: The
EEPROM chip is faulty.
Measure: Contact Huawei
technical support for repair.
The UPS
Possible cause: The load
automatically
exceeds the rated inverter
starts after
loading capacity.
shutdown.
Measure: Reduce the load or
The UPS
replace the UPS with a
transfers to
larger-capacity UPS.
another working
mode or shuts
down.
The UPS startup
Possible cause: The load
is not allowed.
exceeds the rated bypass
C Alarm Handling
blocked.
The fan is abnormal.
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.
Clean off the foreign
objects around the fan. If
the alarm persists, contact
Huawei technical support
for repair.
Parallel cables are
incorrectly connected.
The lengths of parallel
cables vary greatly.
Reconnect cables.
The lengths of parallel
cables vary within a
range of 5%.
135