Huawei UPS2000-G-3KRTL-V2 User Manual page 147

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Alarm ID
Alarm
(Alarm
Name
ID-Alarm
Cause)
0135-01
Ambient
underhumidit
y
0136-01
Faulty
temperature
and humidity
module
0158-01
On bypass
Issue 07 (2019-12-19)
Alarm
Alarm Clear
Level
Mode
Minor
Minor
Minor
Automatic clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
Repair Proposal
System
Measures:
Possible causes:
Measures:
Possible causes: The
temperature and humidity
module is faulty.
Measures:
If the bypass is
Possible causes:
abnormal, the
UPS may power
off.
Measures:
C Alarm Handling
90%).
The temperature and
humidity transducer is
faulty.
Check the ambient
humidity of the UPS
equipment room.
Replace the temperature
and humidity transducer.
The ambient humidity in
the UPS equipment room
is below the alarm
threshold (default value:
10%).
The temperature and
humidity transducer is
faulty.
Check the ambient
humidity of the UPS
equipment room.
Replace the temperature
and humidity transducer.
Check parameter settings
of the temperature and
humidity transducer.
Replace the temperature
and humidity transducer.
The inverter is not
started.
The load exceeds the
rated inverter loading
capacity.
The inverter is faulty.