Huawei UPS2000-G-3KRTL-V2 User Manual page 134

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Alarm ID
Alarm
(Alarm
Name
ID-Alarm
Cause)
0036-01
Batt. maint.
notif
0040-01
Rectifier fault
0040-02
Rectifier fault
0040-04
Rectifier fault
Issue 07 (2019-12-19)
Alarm
Alarm Clear
Level
Mode
Minor
Automatic clear
Critical Manual
clear/Power-off
clear
Critical Manual
clear/Power-off
clear
Critical Manual
clear/Power-off
clear/Automatic
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
Repair Proposal
System
Measure:
An alarm is
Possible cause: The battery
generated. If the
does not experience shallow
shallow
discharge, and the
discharge test is
maintenance period expires.
not performed
Measure:
for a long time,
Perform the following steps:
the battery power
Click the alarm. The battery
backup function
maintenance menu is
may be affected.
displayed. Perform a shallow
discharge test. The alarm
will be automatically cleared
no matter whether test
conditions are met.
The UPS shuts
Possible cause: The soft-start
down.
resistor is damaged.
The UPS
Measure: Contact Huawei
transfers to
technical support for repair.
another working
mode or shuts
down.
The UPS cannot
Possible causes:
be started.
Measures:
The UPS shuts
Possible causes:
down.
The UPS
transfers to
another working
mode or shuts
down.
C Alarm Handling
Check the mains, and
charge batteries in a
timely manner.
Check the configured
battery capacity.
The mains input
harmonic is large.
The rectifier startup
circuit is damaged.
After you rectify the
fault, restart the UPS.
Contact Huawei technical
support for repair.
The mains experiences
instantaneous
high-voltage impact.
The output has special
loads such as inductive
loads and rectification
127