C Alarm Handling - Huawei UPS2000-G-3KRTL-V2 User Manual

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Alarm ID
Alarm
(Alarm
Name
ID-Alarm
Cause)
Abnormal
0001-01
mains volt.
0001-02
Abnormal
mains volt.
Abnormal
0001-03
mains volt.
0004-01
Mains phase
reverse
Issue 07 (2019-12-19)
Alarm
Alarm Clear
Level
Mode
Minor
Automatic clear
Minor
Minor
Minor
Automatic clear
Copyright © Huawei Technologies Co., Ltd.
C
Alarm Handling
Impact on the
System
The UPS
transfers to
battery mode.
If no battery
is equipped,
the UPS shuts
down.
The rectifier
transfers to
battery mode,
without
affecting the
power supply.
If no batteries
are installed,
the UPS shuts

C Alarm Handling

Repair Proposal
Possible causes:
The mains voltage
exceeds 280 V.
The mains voltage is less
than 80 V.
The mains frequency is
not in the range of 40 Hz
to 70 Hz.
Measures:
Check whether the mains
input voltage is less than
272 V. If not, wait until
the mains recovers.
Check whether the mains
input voltage is greater
than 88 V. If not, wait
until the mains recovers.
Check the mains input
frequency. If the mains
input frequency is
abnormal, wait until the
mains input recovers.
Possible cause: The mains
input three-phase sequence is
incorrect.
Measure: Check that mains
input power cables are
correctly connected.
120