Control Screen - Huawei UPS2000-G-3KRTL-V2 User Manual

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Restoring Factory Settings
You can restore factory settings after the inverter shuts down.

4.6.4 Control Screen

On the Main Menu screen, select Control, and press
Startup Menu
The Startup menu allows you to restart the inverter.
Figure 4-42 Startup screen
Shutdown Menu
The Shutdown menu allows you to shut down the inverter.
Issue 07 (2019-12-19)
Shutdown delay parameters are asynchronous in a parallel system. When used in a parallel system, set
the same shutdown delay parameter for different UPSs.
Shallow Discharge screen
Figure 4-41 Shallow Discharge screen
Test notification parameter
Determine whether to periodically send shallow discharge test notifications. The
values include Disabled and Enabled. The default value is Disabled. If the value is
Enabled, the system sends shallow discharge test notifications. The parameter is
configurable in any mode.
Time interval parameter
Set the time interval for shallow discharge tests. The value ranges from 30Day to
90Day. The default value is 60Day. The parameter is configurable in any mode.
Discharge ratio parameter
Set the proportion of the discharge capacity to the total discharge capacity. The
value ranges from 10% to 50%. The default value is 20%. The parameter is
configurable in any mode.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
. The Control screen is displayed.
72

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents