UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Expected
backup
time
(V/cell)
Table 4-6 Batt. protect first EOD setting values
Expected
backup
time
Low voltage
warning
threshold
(V/cell)
EOD
threshold
(V/cell)
Table 4-7 Balanced mode EOD setting values
Expected
backup
time
Low voltage
warning
threshold
(V/cell)
EOD
threshold
(V/cell)
Issue 07 (2019-12-19)
≤ 0.1 CA
≤ 0.1 CA
1.90
1.85
≤ 0.1 CA
1.85
1.80
EOD auto-start parameter
Determine whether to automatically start inverter output after the mains becomes
normal. The values include Disabled and Enabled. The default value is Enabled.
The parameter is configurable after the inverter shuts down.
Shutdown delay parameter
When the delay time reaches the value after UPS transfers to battery mode, the UPS
powers off. The value ranges from 0S to 600S. The default value is 0S. The value
interval is 30s. For example, the value can be 0s, 30s, 60s, and 90s. If the delay time
is set to 0S, the shutdown delay function is disabled. If the delay time is set to other
values, ensure that backup time is greater than shutdown delay time. Otherwise, the
power supply to loads may be disconnected. The parameter is configurable in
non-battery mode or non-battery ECO mode.
Copyright © Huawei Technologies Co., Ltd.
0.1 CA to
0.5 CA to 1
0.5 CA
CA
0.1 CA to
0.5 CA to 1
0.5 CA
CA
1.90
1.90
1.85
1.83
0.1 CA to
0.5 CA to 1
0.5 CA
CA
1.85
1.85
1.75
1.70
4 Control Panel
1 CA to 3
> 3 CA
CA
1 CA to 3
> 3 CA
CA
1.90
1.90
1.75
1.67
1 CA to 3
> 3 CA
CA
1.85
1.85
1.67
1.65
71