Huawei UPS2000-G-3KRTL-V2 User Manual page 133

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Alarm ID
Alarm
(Alarm
Name
ID-Alarm
Cause)
0032-01
Batt. OVP
0034-01
Remaining
cap. warning
Issue 07 (2019-12-19)
Alarm
Alarm Clear
Level
Mode
Critical Automatic clear
Minor
Automatic clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
Repair Proposal
System
Measures:
An alarm is
Possible causes:
generated, and
the battery
lifespan is
affected.
Measures:
If no action is
Possible cause:
taken, continued
discharge will
result in system
shutdown due to
EOD.
C Alarm Handling
blocked.
The fan is abnormal.
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.
Clean off the foreign
objects around the fan. If
the alarm persists, contact
Huawei technical support
for repair.
The configured number
of batteries is less than
the actual number.
The actual number of
batteries does not meet
specifications.
The charger is abnormal.
Check that the configured
number of batteries
matches the actual
number.
Check that the actual
number of batteries meets
requirements.
Disconnected the external
battery charger, check
whether the alarm is
cleared. If not, contact
Huawei technical support
for repair.
The battery discharge
lasts too long.
The mains input is
abnormal.
The number of batteries
or battery capacity is
incorrectly set.
126