  • Page 1 UPS2000-G1-(6 kVA–10 kVA) V100R001 User Manual Issue Date 2013-07-17 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    This document describes the UPS2000 in terms of its features, performance, appearance, structure, working principles, installation, operation and maintenance (O&M). NOTE Unless otherwise specified, the UPS2000 described in this document refers to the UPS2000-G1-6 kVA and UPS2000-G1-10 kVA. Intended Audience This document is intended for: ...
  • Page 4 This issue incorporates the following changes: Chapter 3 Network Topology This chapter changes the cable colors of the battery. Issue 01 (2012-02-10) This issue is used for first office application (FOA). Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    4.3 Running UPSs in Parallel ..........................24 4.3.1 Starting UPSs in Parallel ........................24 4.3.2 Shutting Down Parallel-Running UPSs ....................25 4.3.3 Exiting a Faulty UPS..........................25 Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 6 6 Troubleshooting .......................... 31 6.1 Identifying the UPS Status ..........................31 6.2 Rectifying Common Faults ..........................33 A Technical Specifications ......................36 B Acronyms and Abbreviations ....................39 Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 7: Safety Precautions

     The UPS input power cable is recommended to be less than 2 meters.  Smoking and fire are forbidden within 3 meters around a UPS. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 8: Precautions For Operating Batteries

    (for example, motors, air conditioners, and printers).  Before using a UPS to support the following equipment, consult Huawei for special requirements on the application, configuration, management, and maintenance of the UPS: Life support equipment −...
  • Page 9: Ups Overview

    The UPS perfectly supports loads that require power supply that has the same phase with the power grid. This feature improves the reliability of the UPS and its static switch. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 10: Output Capacity

    Figure 2-1 shows the UPS2000-G1-(6 kVA–10 kVA). Figure 2-1 UPS2000-G1-(6 kVA–10 kVA) 2.3.2 Panels This section describes the front and rear panels on the UPS. Front panel Figure 2-2 shows the front panel. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 11 Steady on: The UPS is working in BYPASS Bypass indicator bypass mode.  Off: The UPS is not working in bypass mode.  Flashing: The bypass voltage or frequency is abnormal. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 12  If you press this button for 5 seconds, the parameter setting screen is displayed. Rear Panel Figure 2-4 shows the UPS2000-G1-6 kVA rear panel. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Working Principles

    UPS2000-G1-(6 kVA–10 kVA) User Manual 2 UPS Overview Figure 2-4 UPS2000-G1-6 kVA rear panel (1) RS232 port (2) EPO port (3) Parallel control port (4) Fan (5) Input breaker (6) Fuse (7) Surge protection and (8) Output grounding port socket...
  • Page 14  Bypass mode When the UPS is overloaded, overheated, or faulty, and the bypass is normal, the power supply automatically switches to the bypass. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Installation

    Used to check cabinet insulation and cable connection, and measure electronic performance specifications of a device, such as voltage, current, and resistance. Label Used to prepare labels. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 16 Used to heat a heat shrink tubing. Electrician's knife Used to strip cables. Protective gloves Used to protect the hands and the device on which you operate. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 17 Keep the air vents on the front and rear panels unobstructed to facilitate ventilation and heat dissipation. Otherwise, the UPS internal temperature will rise, which will shorten the lifetime of the UPS. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Single Ups Installation Procedure

    Step 3 Secure the UPS to the rack by installing M6 screws in the mounting ears. Figure 3-2 shows how to rack-mount the UPS. Figure 3-2 Rack-mounting the UPS NOTE Four M6 x16 screws and four floating nuts are required. ----End Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 19 Figure 3-3 shows the dimensions of the UPS used for tower-mounting. Figure 3-3 Dimensions of the UPS used for tower-mounting Step 2 Place the UPS on two bases. Figure 3-4 shows how to tower-mount the UPS. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Connecting Power Cables

    Step 1 Switch off the three circuit breakers that respectively control batteries, loads, and AC input. Step 2 Remove the busbar protective cover. Step 3 Connect the ground cable. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 21 The local cable colors prevail. The cable colors in the figure are for reference only. Step 7 Reinstall the busbar protective cover, and secure cables. Table 3-1 describes the recommended cable cross-sectional area and screw models for the UPS. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 22: Connecting Communications Cables

    (PC). Figure 3-6 shows how to connect a communication cable to an RS232 port. Figure 3-6 Connecting a communication cable to an RS232 port Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 23 1 and 3 are short-circuited, the inverter stops, and the bypass is also disabled. In this way, the UPS output stops immediately. Figure 3-8 shows how to connect cables to EPO ports. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 24 Step 3 Connect the signal cable to the SNMP Card. Figure 3-9 shows how to connect a cable to external SNMP card. Figure 3-9 Connecting a cable to external SNMP card Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Connecting The Ups To External Battery Packs

    Figure 3-10 shows how to install a backfeed protection device. Figure 3-10 Installing a backfeed protection device Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Installing Upss In Parallel

    User Manual 3 Installation NOTE The Schneider contactors LC1-D3210M5C and LC1-D5011M5C are recommended for the UPS2000-G1-6 kVA and UPS2000-G1-10 kVA respectively. The contactor specifications are as follows:  Rated voltage: 220 V AC, 230 V AC, or 240 V AC ...
  • Page 27 UPS2000-G1-(6 kVA–10 kVA) User Manual 3 Installation Figure 3-12 Connecting the cables NOTE The local cable colors prevail. The cable colors in the figure are for reference only. ----End Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Operation Instructions

    4.2.1 Starting the UPS Starting the UPS in Normal Mode To start the UPS in normal mode, perform the following steps: Step 1 Switch on the UPS input breaker. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 29 UPS2000-G1-(6 kVA–10 kVA) User Manual 4 Operation Instructions Figure 2-4 and Figure 2-5 show the positions of the input breakers on the UPS2000-G1-6 kVA and UPS2000-G1-10 kVA respectively. Step 2 If the LCD lights up and displays correct information, press the button for 1 second.
  • Page 30: Shutting Down The Ups

    Step 3 Set the UPSs to work in parallel mode. When the LCD displays the standby screen, press the MENU button for 5 seconds. The message "Alarm Silence OK?" is displayed. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Shutting Down Parallel-Running Upss

     After switching on the output breaker of the parallel system, check the output cross current of each UPS. If any output cross current exceeds 3 A, contact Huawei technical support for repair. Otherwise, the inverter will be damaged. ----End 4.3.2 Shutting Down Parallel-Running UPSs...
  • Page 32: Entering A Ups

    UPS input and output, loads, batteries, current UPS status, and real-time alarms, and allows you to set control parameters. It also enables you to query historical alarms. Figure 4-3 shows the LCD menu hierarchy. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 33 UPS2000-G1-(6 kVA–10 kVA) User Manual 4 Operation Instructions Figure 4-3 LCD menu hierarchy Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 34 You can press the MENU button for 0.6 second to turn the LCD to the next page, press the MENU button for 5 seconds to enter a parameter setting screen, and press the button to confirm the settings. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Routine Maintenance

    To ensure human safety and equipment security, observe the following precautions when maintaining batteries in the UPS:  Clean battery shells by using a water-dipped cloth. Oil and organic solvents, such as petrol and diluents are prohibited. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Preventive Maintenance

    5.3 Fan Maintenance Check periodically that fans work properly and air vents are not blocked. If a fan stops running, maintain or replace it in a timely manner. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 37: Troubleshooting

    The buzzer The UPS switches to Output 220.0 V overload buzzes. the bypass after 1 OVER LOAD minute. LINE: on INV.: off BYPASS: on FAULT: on OUTPUT: on Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 38 INV.: on LINE FAIL breaker buzzer beeps BYPASS: flashing for three abnormal consecutive FAULT: off mains times at an OUTPUT: on input interval of 100 Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Rectifying Common Faults

    UPS switches to the normal mode automatically, no measure is required. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 40 After a serious overload Disconnect noncritical condition occurs, the UPS is loads. not restarted and continues to work in bypass mode. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 41 The LCD control board is Contact the local Huawei faulty or is not properly office. connected. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 42: A Technical Specifications

    (automatically (automatically adjusted based on adjusted based on the the load power) load power) Output Rated power 6 kVA / 4.8 kW 10 kVA / 8 kW Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 43 GB/T 3859.2. Acoustical noise < 65 dB Certifi Complies with the EN/IEC 60240-2 cation Safety and regulatory Complies with the EN/IEC 60240-1 Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 44 Communication The UPS supports RS232 and SNMP. Backup time Short backup time: 5 minutes, 10 minutes, etc Long backup time: 2 or 4 hours Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 45: B Acronyms And Abbreviations

    China Compulsory Certification electromagnetic compatibility emergency power-off liquid crystal display operation and maintenance O&M power factor correction protective earth RS232 Recommend Standard 232 SNMP Simple Network Management Protocol Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 46 UPS2000-G1-(6 kVA–10 kVA) User Manual B Acronyms and Abbreviations uninterruptible power system Underwriters Laboratories Inc. Issue 05 (2013-07-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.