Huawei UPS2000-G-3KRTL-V2 User Manual page 86

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Starting the UPS in Normal Mode
Step 1 Close the external battery circuit breaker (if there is), or connect battery cables.
Step 2 Close the UPS AC input circuit breaker K.
The initialization screen is displayed.
Step 3 The UPS enters bypass mode. The UPS sL delivers bypass voltages, and pL delivers no
voltage. When the initialization is complete, perform the following operations:
Step 4 Start the UPS in normal mode by using one of the following methods:
Step 5 When the UPS runs properly, close the UPS AC output circuit breaker Q, and start the loads.
----End
Starting the UPS in Battery Mode
Step 1 Close the external battery circuit breaker (if there is), or connect battery cables.
Step 2 Press
Issue 07 (2019-12-19)
Perform
Step 2
when there are two mains inputs. In the case of one mains input, you need only to close
the UPS mains input circuit breaker.
Initial startup
On the Settings wizard screen, set the language (the preset language is English), system
parameters, and battery parameters. Press
Non-initial startup
When the initialization is complete, the standby screen is displayed. On the standby
screen, press
to enter the main menu. Choose Main Menu > Settings > System
Parameters > Output to view output settings: if the system uses three-phase input
single-phase output or single-phase input single-phase output, Output mode is set to
Single-phase; if the system uses three-phase input three-phase output, Output mode is
set to Three-phase. Voltage level and Frequency level are set based on the rated
voltage and frequency. Press ESC to return to the standby screen.
On the standby screen, hold down
you hear a beep sound. The startup screen is displayed. If the UPS starts successfully, it
enters normal mode.
On the standby screen, hold down
Control menu, and press
successfully, it enters normal mode.
The two methods in
Step 4
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.
on the control panel.
Copyright © Huawei Technologies Co., Ltd.
more than 5 seconds. Release the button when
to enter the main menu. Select Startup in the
. The Starting message is displayed. If the UPS starts
are called "startup operations" in this section.
. The standby screen is displayed.
5 Operations
79