Huawei UPS2000-G-3KRTL-V2 User Manual page 68

Two live wires
Table of Contents

Advertisement

UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
Communication Card Screen
Issue 07 (2019-12-19)
If an SNMP card is connected, set the following parameters:
Figure 4-27 SNMP card settings
IP address parameter
Set an IP address for the SNMP card. The value ranges from 0.0.0.0 to
255.255.255.255. The default value is 192.168.0.10.
Subn. mask parameter
Set a subnet mask for the SNMP card. The value ranges from 0.0.0.0 to
255.255.255.255. The default value is 255.255.255.0.
Gateway parameter
Set a gateway address for the SNMP card. The value ranges from 0.0.0.0 to
255.255.255.255. The default value is 192.168.0.1.
If a Modbus card is connected, the following parameters are displayed:
Figure 4-28 Modbus card settings
Comm. address parameter
Set a communications address for the Modbus card over the dual in-line package
(DIP) switch on the Modbus card. The value cannot be changed on the LCD.
Baud rate parameter
Set a baud rate for the Modbus card over the DIP switch on the Modbus card. The
value cannot be changed on the LCD.
If a dry contact card is connected, set the following parameters:
Figure 4-29 Dry contact card settings
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents