C7 Digital Input/Output
5.2

Digital Output Function

Characteristics
Special Feature
5
5-4
The digital output function has the following characteristics:
16 outputs, isolated.
Output current: 0.5 A
Nominal load voltage: 24 VDC
Suitable for solenoid valves and d.c. contactors.
The digital outputs may be briefly activated under the following conditions:
Applying the DI/DO power supply (independently of the 24V/GND
wiring)
Applying the 24V/GND, if the DI/DO power supply is already wired.
A pulse can be approximately 50 µs within the permissible output voltage
range. You must observe this when using digital outputs in conjunction with
high speed counters.
C7-626 / C7-626 DP Control Systems