Recommendations For Ac Power Supply - Huawei AR100 Series Hardware Installation And Maintenance Manual

Enterprise routers
Hide thumbs Also See for AR100 Series:
Table of Contents

Advertisement

Huawei
AR100&AR120&AR150&AR160&AR200&AR1200&AR
1600&AR2200&AR3200&AR3600 series Enterprise
Routers
Hardware Installation and Maintenance Guide
protect independent devices. Configure the current-carrying capacity of the protection switch
of the equipment room for more than that of the devices.
Table 9-19
Table 9-19 Voltage range of AC power supply
Item
AC power capacity to
support the devices
AC power capacity to
support the power modules
and important buildings
Frequency of alternating
current
Voltage wave shape sine
distortion
The automated electric generator must have a standard interface that supports
telecommunication protocols, remote telecommunication, monitoring, and control.
AC power cables should meet the following specifications:
l
AC neutral should have a conductor with the same cross section as the phase line.
l
AC cables should have non-flammable insulation. The layout of AC cables should
comply with local regulations. Low-voltage power distribution rooms should comply
with local regulations.

9.3.2.2 Recommendations for AC Power Supply

The following are recommendations for the AC power supply.
l
If the voltage of the power mains that supply power directly to devices exceeds the rated
voltage by -10% to 5%, or exceeds the voltage range that devices can support, a voltage
regulating device or voltage stabilizing device is required.
l
If the mains do not supply power for the device directly, or if the mains voltage exceeds
the rated voltage by -15% to 10% or exceeds the input voltage range of the DC power
supply, a voltage regulating device or voltage stabilizing device is required.
l
A UPS or inverter power supply system is required to provide uninterrupted AC power
to support the telecommunication load.
l
If abnormalities occur on the mains, telecommunication servers should be equipped with
a self-supplied electric generator to support the key telecommunication load. The
capacity should be not less than 150% to 200% of the total uninterruptible power supply.
l
Storage batteries are usually installed in a parallel connection of two groups. UPS
storage batteries are generally installed in one group. The redundancy required for the
UPS can rely on concatenation or parallel connection. When an inverter or a UPS is
used, the active inverter is determined by the maximum power and a backup inverter is
required.
Issue 05 (2018-07-30)
lists the voltage range of the AC power supply for the devices.
Requirements
-10% to +5% of the rated voltage
-15% to +10% of the rated voltage
-4% to +4% of the rated value
Within 5% of the rated voltage
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Appendix
188

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents