Requirements For Esd Prevention; Electromagnetism Requirements For The Equipment Room; Requirements For Lightning Proof Grounding - Huawei AR100 Series Hardware Installation And Maintenance Manual

Enterprise routers
Hide thumbs Also See for AR100 Series:
Table of Contents

Advertisement

Huawei
AR100&AR120&AR150&AR160&AR200&AR1200&AR
1600&AR2200&AR3200&AR3600 series Enterprise
Routers
Hardware Installation and Maintenance Guide
Chemical active
material
Cl
2
Take the following measures to meet the requirements:
l
Avoid constructing the room near a place where the corrosive gas concentration is high,
such as a chemical plant.
l
Ensure the air intake vent of the room is in the prevailing upwind direction from any
pollution source.
l
Place batteries in different rooms.
l
A professional service should monitor the corrosive gas conditions regularly.

9.3.1.6 Requirements for ESD Prevention

The absolute value of electrostatic voltage must be less than 1000 V.
Take the following measures to meet this requirement:
l
Train operators about ESD prevention.
l
Keep the correct humidity level in the equipment room to reduce the impact of static
electricity.
l
Lay out an ESD floor in equipment rooms.
l
Wear ESD shoes and clothing before entering equipment room.
l
Use ESD tools, such as wrist straps, tweezers, and pullers.
l
Ground all conductive materials in the room, including computer terminals. Use ESD
worktables.
l
Keep non-ESD materials (such as common bags, foam, and rubber) at least 30 cm (11.81
in.) away from boards and ESD-sensitive components.

9.3.1.7 Electromagnetism Requirements for the Equipment Room

All interference sources, inside or outside the equipment room, can cause equipment problems
with capacitive coupling, inductive coupling, electromagnetic wave radiation, and common
impedance (including grounding system) coupling. Prevent the interference using these
approaches:
l
Take effective measures against electrical interference from the power supply system.
l
Do not use the working ground of the equipment as the same ground for surge
protection. Separate them as far as possible.
l
Keep the equipment far away from high-power radio transmitters, radar units, and high-
frequency and high-current equipment.
l
Use electromagnetic shielding if necessary.

9.3.1.8 Requirements for Lightning Proof Grounding

Table 9-18
Issue 05 (2018-07-30)
Unit
3
mg/m
lists the requirements for lightning proof grounding.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Concentration
≤0.01
9 Appendix
184