Table 11 Troubleshooting Table - Vaisala VaiNet RFL100 User Manual

Wireless
Hide thumbs Also See for VaiNet RFL100:
Table of Contents

Advertisement

RFL100 User Guide
6. Troubleshooting
6.1 Problem situations
Table 11 Troubleshooting table
Problem
Display shows one or more
error codes.
You are adding a new RFL100
data logger to the system but it
is not coming up as a New
Device in viewLinc.
56
Possible cause
Various causes.
RFL100 is not in range of an
AP10 that has installation
mode turned on, and capacity
to add more data loggers
(maximum 32 for each AP10).
RFL100 is connected to an
AP10 that is not connected to
viewLinc.
RFL100 has been previously
accepted to a different
viewLinc system.
RFL100 has joined an AP10 but
has not been accepted to the
viewLinc system. The AP10 is
no longer in range, but RFL100
cannot change to a different
access point as it is pending to
be accepted to the system.
M211861EN-D
Solution
Check meaning of the error
code(s) and proceed
accordingly. See
Error codes
(page
57).
Turn on installation mode in an
AP10 that is within 100 m of the
data logger, and has capacity
to add more data loggers.
Verify the following:
• AP10 is connected to the
network and has an IP
address.
• AP10 is configured to
connect to the correct
viewLinc Enterprise Server.
• viewLinc connection of the
AP10 is OK.
Press the Release button of the
RFL100 and verify that the
message NWK REL appears on
screen. The RFL100 is now
ready to join any AP10 that is in
installation mode.