Technical Data
3.4

Operating conditions

Definition acc.
Site altitude
Ambient conditions during operation
Climate
Mechanical
Contamination
Ambient conditions during transport
Climate
Mechanical
Contamination
Ambient conditions for the storage
Climate
Mechanical
Contamination
Type of protection
Environment
Definition acc.
EMC emitted interference
Cable-based interferences
Radiated interferences
Interference immunity
Static discharges
20
Standard
EN 61800-2
EN 61800-5-1
Temperature
EN 60721-3-3
Humidity
Track
Germ. Lloyd
Vibration
EN 60721-3-3
Gas
Solids
Tempera-
ture
Humidity
Vibration
EN 60721-3-2
Surge
Gas
Solids
Tempera-
ture
Humidity
EN 60721-3-1
Vibration
Surge
Gas
Solids
EN 60529
IEC 664-1
EN 61800-3
EN 61000-4-2
Class
Inverter-product standard:
Rated specifications
Inverter-product standard:
General safety
max. 2000 m above sea level
With site altitudes over 1000 m a derating of 1 %
per 100 m must be taken into consideration.
(with temperature over 45°C to max. 55°C
3K3
a derating of 5 % per 1 K must be taken into
3K3
5...85 % (without condensation)
EN50155
max. amplitude of a vibration 1 mm
Part 7-3
max. acceleration amplitude 7 m/s²
3M4
3C2
3S2
2K3
(without condensation)
2K3
max. vibration amplitude 3.5 mm
2M1
max. acceleration amplitude 15 m/s²
2M1
2C2
2S2
1K4
(without condensation)
1K3
max. amplitude of a vibration 1 mm
1M1
max. acceleration amplitude 7 m/s²
1M1
1C2
1S2
IP20
Pollution degree 2
Inverter-product standard: EMC
with EMC filter and ferrite rings
C2
with EMC filter and ferrite rings
EN 61800-3
8 kV
AD (air discharge) and CD (contact dis-
Instructions
extended to -10...45 °C
consideration)
(5...13 Hz)
(13...200 Hz)
(2...9 Hz)
(9...200 Hz)
max. 100 m/s²; 11 ms
(5...13 Hz)
(13...200 Hz)
max. 100 m/s²; 11 ms
charge)