Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

Connection Power Unit R6-N
4.4.5

Regenerative operation at parallel operation of up to two R6-N with decoupling diodes

(Parallel operation with an error at current sharing of the R6-N units of ≤10 % and max. power
ratio from inverter to regenerative units 1.7:1)
2
1
L1
L2
L3
PE
1
Line fuses
2
Line contactor with protective
wiring
2a
Contactor with protective
wiring
3)
3
Main fuses type gR
4
Radio interference filter E6
5
Mains choke xxZ1B04-1000 harmonic filter xxZ1C04-1000
1)
The cable cross-section may not be smaller than 10 mm². It must be dimensioned for the DC rated
current of the load. Otherwise there are fuses in the DC circuit (10) necessary The indicated maximum
protection for the connected frequency inverter must be observed!
2)
If the inverter current > current of the COMBIVERT R6-S it must be wired at an external terminal (12).
3)
The contactor may only be connected if the precharging in the DC circuit is completed. Note the per-
missible DC link capacity of the charging circuit of the inverter!
36
5
4
L1
L1'
L2
L2'
L3
L3'
5
6
5)
7
8
9
5)
7
3
X2D
L12
L22
L32
7
3
X2D
L12
L22
L32
2a
6
PE
L1
8
L2
L3
9
2a
10
6
PE
L1
8
L2
L3
9
10
Choke (xxZ1F04-1010)
COMBIVERT R6-N with
DC fuses
Frequency inverter (typ
A1/A2 or B1/B2) same
type and size
Ferrite (optional)
++
++
14
- -
- -
11
++
++
13
14
- -
- -
9
11
- -
-
PE
9
12
- -
-
PE
10
Motor
6)
11
DC fuses type aR/gR
12
DC fuses type aR/gR
13
External terminal block
14
Decoupling diodes (see annex)
6) 8)
continued on the next page
1) 5)
5)
2)